Voltage/Current Isolator will isolate DC voltage or current signals, convert them into required signals and
transmit to other instrument. It can be used together with modular instrumentation and DCS, PLC and
other systems, to offer signal isolation, signal conversion, signal distribution, signal processing and other
functions to field instrument, thereby enhancing the immunity of automatic control system in the industrial
production process, and ensuring system stability and reliability. This product has many varieties, such
as 1 in/1 out, 1 in/2 out, 2 in/2 out, withinput/output magnetic isolation.
Input | |
Input signal | 4-20mA,0-20mA,0-5V,1-5V,0-10V |
Input resistance | Impedance ≤50Ω, voltage Impedance ≥250 KΩ |
Maximum input current / voltage | ≤30mA/≤10.5V |
Current isolator output | |
Output signal | 0-20mA,0-20mA,0-5V,1-5V,0-10V |
Output load | 4-20mA, 0-20mA load resistance RL≤400Ω; |
0-5V, 1-5V load resistance RL≥250KΩ, 0-10V load resistance RL≥500KΩ | |
Voltage isolator output | |
Output signal | 0-20mA,0-20mA,0-5V,1-5V,0-10V |
Output load | 4-20mA, 0-20mA load resistance RL≤400Ω; |
0-5V, 1-5V, 0-10V load resistance RL≥20KΩ | |
Power supply | |
Power supply | DC20-32V |
Power consumption | Single Output Power: ≤0.8W; Dual Output Power: ≤1.0W |
Other parameters | |
Insulation resistance (between input / output / power supply) | ≥100MΩ (500VDC) |
Dielectric strength (between input / output / power supply) | 2000Vrms (1 min, no spark) |
Operating temperature | -10 ~ 50 °C (no condensation, no freezing) |
Relative humidity | 25%~85%RH |
Storage temperature | -10 ~ 60 °C (no condensation, no freezing) |
Temperature drift | 0.0075%FS/ºC |
Mounting style | 35mmDIN rail mounting |
Dimensions | 13 * 108 * 121.2mm (W * H * D) |
Transmission accuracy | 0.15%FS |
(20 °C) | |
Response time | ≤2ms |
Weight | Approximately 130 g |
Electromagnetic compatibility | In line with GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Field devices applicable | DC voltage / current source |
Overseas Service Center Address:
Singapore/ Philippines/ Malaysia/ Kroea/ Indonesia/ Germany/ India
FAQ:
Q: How long will you give me the reply?
A: we will contact you in 3 hours as soon as we can.
Q:Could I visit your factory?
A: Sincerely invite you to visit our factory,Our factory and office are all in Hangzhou,Zhejiang.
Q: Do you provide samples ?
A: Yes,we have materials in stock to help you to get the samples as soon as we can.
Q: How about the quality of the managements ?
A: We have a complete quality control system , all of our products will be fully pre-inspection by QC departments before shipping to you . We have the certification of ISO,CE we could send the certification test of our company to you.
Q: What is your terms of payment ?
A: We could accept T/T, Paypal, WU ,Credit Assurance
Q: What is the warranty for your product ?
A: Warranty: 2 years, Lifetime maintenance.
Q: How soon can you arrange the production?
A: Once getting your product confirmation and receiving your payment, we will arrange the production immediately. For some products we have it in stock.
Q: Could you provide me the shortest lead time?
A: For somre standard products we have it in stock . Pls tell me your detailed requirements, we will send to you as early as we can.